SUN-12K-SG04LP3-EU Hybrid Solar Inverter Three Phase
Model Number: 12KW SUN-12K-SG04LP3-EU
Output Voltage: 220/380V, 50/60Hz
Max Efficiency: 97.6%
Colorful LCD Touch Screen
Protection Degree: IP65
Warranty: 5 years (10 years optional)
Place of Origin: China
Description
The hybrid inverter 12kw SUN-12K-SG04LP3-EU is the hybrid three phase low voltage 48V type, it supports three phase unbalanced output. It is compact and easy to install on the wall. The ingress protection rate is IP65, you can install it outdoor. The hybrid inverter has many communication ports which makes it flexible and smart to connect to batteries and is managed by smartphones via App remotely. We provide comprehensive certificates to ensure you import smoothly. Feel free to reach out.
Technical Data
- Battery Input Date
- PV String Input Date
- AC Input/Output Date
- General Data
Model | SUN-5K-SG04LP3-EU | SUN-6K-SG04LP3-EU | SUN-8K-SG04LP3-EU | SUN-10K-SG04LP3-EU | SUN-12K-SG04LP3-EU |
Battery Input Data | |||||
Battery Type | Lead-acid or Lithium-ion | ||||
Battery Voltage Range(V) | 40-60 | ||||
Max.Charging Current(A) | 120 | 150 | 190 | 210 | 240 |
Max.Discharging Current(A) | 120 | 150 | 190 | 210 | 240 |
Charging Strategy for Li-ion Battery | Self-adaption to BMS | ||||
Number of battery input | 1 |
Model | SUN-5K-SG04LP3-EU | SUN-6K-SG04LP3-EU | SUN-8K-SG04LP3-EU | SUN-10K-SG04LP3-EU | SUN-12K-SG04LP3-EU |
PV String Input Data | |||||
Max. PV Access Power (W) | 10000 | 12000 | 16000 | 20000 | 24000 |
Max PV Input Power(W) | 6500 | 7800 | 10400 | 13000 | 15600 |
MaxPV Input Voltage(V) | 800 | ||||
Start-up Voltage(V) | 160 | ||||
MPPT Voltage Range(V) | 200-650 | ||||
Rated PV Input Voltage(V) | 550 | ||||
Max. Operating PV Input Current (A) | 13+13 | 26+13 | |||
Max. Input Short-Circuit Current (A) | 17+17 | 34+17 | |||
No.of MPP Trackers/No.of String Per MPP Tracker | 2/1+1 | 2/2+1 |
Model | SUN-5K-SG04LP3-EU | SUN-6K-SG04LP3-EU | SUN-8K-SG04LP3-EU | SUN-10K-SG04LP3-EU | SUN-12K-SG04LP3-EU |
AC Input/Output Data | |||||
Rated AC Input/Output Active Power(W) | 5000 | 6000 | 8000 | 10000 | 12000 |
Max AC Input/Output Apparent Power (VA) | 5500 | 6600 | 8800 | 11000 | 13200 |
Peak Power (off-grid)(W) | 2 times of rated power, 10s | ||||
Rated AC Input/Output Current(A) | 7.6/7.2 | 9.1/8.7 | 12.1/11.6 | 15.2/14.5 | 18.2/17.4 |
Max AC Input/Output Current(A) | 8.4/8 | 10/9.6 | 13.4/12.8 | 16.7/15.9 | 20/19.1 |
Max Continuous AC Passthrough (grid to load)(A) | 45 | ||||
Rated Input/Output Voltage/Range(V) | 220/380V,230/400V 0.85Un-1.1Un | ||||
Grid Connection Form | 3L+N+PE | ||||
Rated Input/Output Grid Frequency/Range | 50/45-55, 60/55-65 | ||||
Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | ||||
Total Current Harmonic Distortion THDi | <3% (of nominal power) | ||||
DC Injection Current | <0.5%ln |
General Data | |||||
Operating Temperature Range | -40 to +60℃, >45℃ Derating | ||||
Permissible Ambient Humidity | 0-100% | ||||
Permissible Altitude | 2000m | ||||
Noise | ≤ 55 dB(A) | ||||
Ingress Protection(IP) Rating | IP 65 | ||||
Inverter Topology | Non-Isolated | ||||
Over Voltage Category | OVC II(DC),OVC III(AC) | ||||
Cabinet size(W*H*D)[mm] | 422×658×254(Excluding connectors and brackets) | ||||
Weight[kg] | 38 | ||||
Warranty | 5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
||||
Type Of Cooling | Intelligent air cooling | ||||
Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
||||
Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
Hybrid Inverters Details
On Off Grid
Deye Hybrid Inverter Features
-
100% unbalanced output, each phase; Max. output up to 50% rated power
-
AC couple to retrofit existing solar system
-
Max. 10 pcs parallel for on-grid and off-gridoperation; Support multiple batteries parallel
- Max. charging/discharging current of 240A
- Support storing energy from diesel generator
- 48V low voltage battery, transformer isolation design
- 6 time periods for battery charging/discharging